JAVAC Online Three Phase UPS JV33 160000VA


Model: JV33-160

Download Product Datasheet

1,216,380 EGP Inc. VAT

 

Overview
PresentationProduct features:

AC/AC efficiency up to 96%, less TCO and more energy savings.
Output power factor up to 1.0, more powerful to connect more critical loads.
Green energy :
3-level IGBT technology for higher efficiency and minimal interference with the grid
Super wide input voltage range %25+~%60- for greater adaptability to the grid.
Dual DSP control for high performance Intelligent fan speed control reduces noise and extends fan life
Advanced technology:
Anti-corrosion resistant coating for all printed circuit boards Complete protection with input, output, bypass, maintenance bypass and battery switch
ECO mode and EPO function.
Lead timeUsually in Stock

 

INPUT
Voltage (Vac)380/400/415 (138~485 L-L)
Frequency (Hz)40~70
Power Factor≥0.99
Phase3φ4W+PE
THDi at full linear load<3%

 

BYPASS
Bypass Voltage (Vac)380/400/415: -20%~+15%
Frequency Range (Hz)50/60(±5%/±10%)
Overload≤130%: long run;
130%< load ≤150%: 5min; 150%< load ≤200%: 1s; 200%< load≤300%: 100ms; >300%: immediately.

 

OUTPUT
Capacity (kVA)160
Power Factor1 (0.5 leading to 0.5 lagging)
Voltage (Vac)380/400/415±1%
Frequency (Hz)50/60±0.1% (Battery mode)
Phase3φ4W+PE
Three Phase Difference≤1%
WaveformPure sine wave, THDv<1% at linear load,THDv<3% at non-linear load
Transfer Time (ms)0
AC-AC Efficiencyup to 96.5%
Overload*101-105% Long run,
106-110% load for 60 minutes, 111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass

 

BATTERY
Battery Voltage (Vdc)±240(±168 ~±288 adjustable)
BATT TypeExternal
Charging Current (A) MAX60

 

GENERAL
Communication InterfaceRS485, MODBUS, dry contact
(RS232, BMS,SNMP, expend dry contact card are optional in slot)
Display7-inch touch screen+LED+LED bar
AlarmAC input abnormal, low battery, overload, failure
ProtectionOutput short-circuit, overload, over-temperature, battery low voltage, output over/low voltage
Noise (dB)<65
Altitude(m)0-2000 no derate. 2000-3000 m derate power by 1 % per each 100 m increase
IP20
Working Temperature (°C)0 ~ 40 no derate,40~50 auto derate.
Relative Humidity0 ~ 95%, no condensation
Dimension (W×D×H)(mm)600×1000×1600
Weight (kg)260